HVD1-12KV 1250A 25KA VCB vacuum circuit breaker with copper parts 210mm phase distance
Vacuum Circuit Breaker accept customized order according to technical drawing or samples.
HVD1-12(VS1-12) type indoor AC HV vacuum circuit breaker (hereinafter referred to as circuit breaker) are suitable for 12kV air-insulated indoor switchgears, used as protection and control unit of power equipment of industrial& mining enterprise. Due to the super excellence, it is especially for location where requires the frequent operation of rated working current or multi breaking short circuit current.
The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body, servers as not only fixed installation, but also the handcart unit through equipping with a special propelling mechanism.
2. Service conditions
3.1 Environment temperature:-15℃~+40℃;
3.2 Environment humidity: Daily average relative humidity:≤95%, monthly average relative humidity:≤90%; Daily average saturated vapor pressure:≤2.2×10-3Mpa,monthly average saturated vapor pressure:≤1.8×10-3Mpa;
3.3 Altitude: Not exceed 1000m;
3.4 Earthquake intensity: Not exceed°ree;
3.5 Service location: No water, flammable or explosive matter, chemical corrosive gas or drastic vibration.
3.1 Environment temperature:-15℃~+40℃;
3.2 Environment humidity: Daily average relative humidity:≤95%, monthly average relative humidity:≤90%; Daily average saturated vapor pressure:≤2.2×10-3Mpa,monthly average saturated vapor pressure:≤1.8×10-3Mpa;
3.3 Altitude: Not exceed 1000m;
3.4 Earthquake intensity: Not exceed°ree;
3.5 Service location: No water, flammable or explosive matter, chemical corrosive gas or drastic vibration.
Parameter |
||||||
1 |
Rated voltage |
KV |
12 |
|||
2 |
Rate voltage |
Hz |
50 |
|||
3 | Rated lightning impulse withstand voltage(1min) | KV | 75 | |||
4 | Rated short-time power frequency withstand voltage (1min) | KV | 42 | |||
5 | Rated short-circuit breaking current | KA | 20 | 25 | 31.5 | 40 |
6 | Rated current | A | 630,1000,1250 | 630,1000,1250,1600 | 1250,1600,2000,2500 | 1600,2000,2500,3150 |
7 | Rated peak withstand current | KA | 50 | 63 | 80 | 100 |
8 | Rated shorted-time withstand current | KA | 20 | 25 | 31.5 | 40 |
9 | Rated shorted-time making current(peak) | KA | 50 | 63 | 80 | 100 |
10 | Power frequency withstand voltage of secondary circuit(1min) | V | 2000 | |||
11 | Rated operation sequence | Off-0.3s-On&Off-180s- On& Off Off -180s- On& Off -180s- On& Off* | ||||
12 | Rated breaking current of capacitor bank | A | 630/400(40kA 800/400) | |||
13 | Opening time(rated voltage) | ms | 20~50 | |||
14 | Closing time(rated voltage) | ms | 30~70 |
Packing & Delivery
Strong package, Safety first.
Inside with foam to support the product, put it in carton or wooden box, fixed it on pallet.
As long as possible to keep the products safe until it arriving customer's warehouse.
Clearly marking label outside of package, customers will be easy to identify their goods.
As long as possible to keep the products safe until it arriving customer's warehouse.
Clearly marking label outside of package, customers will be easy to identify their goods.
Our Company
20000 M2 of JUCRO Electric company land
1500 M2 of office building
5000 M2 of workshop building
Inside of JUCRO Electric office building
Inside of JUCRO Electric office building
JUCRO Electric office work area
Workshop
Vacuum Interrupter Workshop
Accept customized order.
Design the Vacuum Interrupter for you.
Design the Vacuum Interrupter for you.
VCB Production Line
VCB Vacuum Circuit Breaker production Line.
VCB Vacuum Circuit Breaker production Line.
VCB Vacuum Circuit Breaker production Line.
Quality Inspection
Carefully inspection of each product, Quality guaranteed
completely data records of entire process , all the product data can be traced.