Transformer Neutral BZJ 110V 220V Series Point of Complete Sets of Equipment From Jucro Electric
- Model
- BZJ 110V 220V
Review
Description
BZJ-110/220 series transformer neutral point of complete sets of equipment according to DL/T620-1997 <overvoltage protection and insulation coordination of> Regulations on the 110kV/220kV transformer neutral point of power network uses the gap protection of AC electrical apparatus manufacturing , and in accordance with the China State Grid Corp in 2005 June published <Eighteen grid major anti accident measures to prevent the requirements of grounding grids and overvoltage accidents> in the process if design . Application of 110kV and 220kV effective grounding power network without transformer neutral point grounding overvoltage protection.
In order to make 110kV transformer neutral point of 220kV substation equipment performance is reliable, convenient installation, commissioning and operation layout is simple and beautiful, the company also introduced the transformer neutral point transformer neutral point rod gap, gap current transformer, isolating switch, lighting arrester, terminal box and a mounting bracket and other electrical equipment in one of the complete sets of equipment.
The user can choose the transformer neutral point of pure clearance overvoltage protection scheme, also can choose the gap and Arrestor in parallel, collaborative protection scheme. Lighting arrester and the isolation switch according to the need of the project, with flexible group. The actuator isolation switch can be operated manually or electrically. Electrical and mechanical properties of all the products are finished debugging and full set of test before leaving the factory, but also convenient in use and correction.
The main parameters of transformer neutral point bar internal number
Nominal clearance Voltage(KV) |
Rated system Voltage(KV) | The electrode gap distance Range | The power frequency discharge voltage Range | Insulating electronic The creeppage distance | Transformer Capacity |
Air pollution level |
Electrode |
72.5 |
110 | 90-135 | 50-63 | 1813 | 20 |
Ⅲ |
Hemispere |
72.5 |
110 | 90-135 | 50-63 | 2248 | 20 |
Ⅳ |
Hemispere |
126 |
220 | 280-330 | 100-127 | 3150 | 20 |
Ⅲ |
Hemispere |
126 | 220 | 280-330 | 100-127 | 3906 | 20 | Ⅳ | Hemispere |
The main parameters of lighting protection technology
Norminal system Voltage(KV) |
Type of surge arrester | Arrester rating Voltage | DC 1mA reference Voltage greaterthan | 8/20 lighting impulse current residual voltage |
2ms square wave A |
4/big electric current(KV) |
110 | YH1.5W-60/144 | 60 | 86 | 144 | 400 | 10(65) |
110 | YH1.5W-72/185 | 72 | 105 | 186 | 400 | 10(65) |
110 |
YH1.5W-737/200 | 73 | 107 | 200 |
400 |
10(65) |
220 |
YH1.5W-144/320 | 144 | 205 | 320 |
400 |
10(65) |
The main parameters of GW13
Item |
Unit | Parameters |
||
The product model | GW17-72.5 | GW17-126 | ||
Rated voltage | KV | 72.5 | 126 | |
Rated Current | A | 630 | ||
Rated peak withstand current | KA | 50 | ||
Rated short-time withstand current | KA | 20 | ||
Rated short duration | S | 4 | ||
Rated short-circuit withstand voltage | KV | 200 | 200 | |
Rated lighting impluse withstand voltage | KV | 385 | 625 | |
Horizontal and vertical | N | 1000 | 1000 | |
Horizontal | 750 | 750 | ||
vertical force | 1000 | 1000 | ||
Mechnical life |
3000 |
|||
With the motor structure switching time |
S | 7.5±1(3.75±0.5) |
||
Weight |
KG | 120 | 155 |
The main parameters of GW8
Item | Unit | Parameters | ||
The product model | GW8-72.5 | GW8-126 | ||
Rated voltage | KV | 72.5 | 126 | |
Rated Current | A | 630 | ||
Rated peak withstand current | KA | 50 | ||
Rated short-time withstand current | KA | 20 | ||
Rated short duration | S | 4 | ||
Rated short-circuit withstand voltage | KV | 200 | ||
Rated lighting impluse withstand voltage | KV | 385 | 625 | |
Rated static mechanical load of terminal | Horizontal and vertical |
N | 1000 |
|
Horizontal |
750 |
750 | ||
vertical force |
1000 |
|||
Mechnical life | Times | 3000 | ||
With the motor structure switching time | S | 7.5±1(3.75±0.5) | ||
Weight | Kg | 90 | 105 |
Strong package, Safety first.
As long as possible to keep the products safe until it arriving customer's warehouse.
Clearly marking label outside of package, customers will be easy to identify their goods.
Vacuum Interrupter Workshop
Design the Vacuum Interrupter for you.